Skip to content

GFE660PSC Perkins Diesel Generator - 590kVA

Call Now

The 551-1100kVA GFE Perkins Powered range can be depended on for continuous and emergency power supply in a variety of engineering projects including hospitals, factories, data centres and banks. Driven by high performance Perkins engines, the range is designed to protect institutions from the potential damage that power interruptions cause.

Model reference GFE660PSC (Canopied) / GFE660PSO (Open)
Engine Perkins 2806A-E18TAG1A
Alternator Stamford S5L1D-E4
Control panel Deepsea
Frequency 50Hz
Engine speed 1500rpm
Phase / Poles 3-Phase / 4-Pole


Ratings

kWe kVA
Prime Power (PRP) 480 600
Standby Power (ERP)
528 660


Voltage
400V
Rated current 952
Fuel consumption 123 @100% load L/h

 

Overall dimensions

Frame type Dimensions Weight Base tank
@100% load

(L x W x H) mm kg Litres
Canopied 4600 x 1843 x 2530 5865 750


Datasheets

 Generator: Engine: Alternator:
600kVA GFE660PSC Perkins 2806A-E18TAG1A Stamford S5L1D-E4