GFE Cummins-Powered 1000kVA Diesel Generator - GFE1100CSC
The GFE1100CSC, powered by a KTA38-G5 Cummins engine, is rated at 1100kVA standby power and produces 1000kVA of prime power, providing reliable electricity for large industrial and commercial operations. Designed for continuous use, it delivers consistent performance for factories, data centres, hospitals, and commercial facilities. The Cummins engine ensures fuel efficiency, low emissions, and minimal maintenance. Advanced control systems allow precise monitoring of load and performance. Its durable, low-noise design enables installation in a variety of environments. Suitable for temporary or permanent deployment, the GFE1100CSC safeguards operations against power interruptions, offering a dependable high-capacity diesel power solution for demanding applications.
| Model reference | GFE1100CSC (Canopied) |
| Engine | Cummins KTA38-G5 |
| Alternator | Stamford S6L1D-E4 |
| Control panel | Deepsea DSE7310/20 |
| Frequency | 50Hz |
| Engine speed | 1500rpm |
| Phase / Poles | 3-Phase / 4-Pole |
Ratings
| kWe | kVA | |
| Prime Power (PRP) | 800 | 1000 |
|
Standby Power (ERP) |
880 | 1100 |
|
Voltage |
400V |
| Rated current | 1443 Amps |
| Fuel consumption | @100% load L/h 209 |
Overall dimensions
| Frame type | Dimensions | Weight | Base tank @100% load |
| (L x W x H) mm | kg | Litres | |
| Canopied | 5450 x 2270 x 2550 | 11,100 | |
Datasheets
| Generator: | Engine: | Alternator: |
| 1000kVA GFE1100CSC | Cummins QSK19-G4 | Stamford S5L1D-F4 |
![]() |
![]() |
![]() |
Choose options


Unsure What Size Generator You Need?
Selecting the correct generator size starts with understanding your power requirements. Our kVA calculator allows you to calculate the kVA needed based on your power requirements, helping you choose a generator that fits your application.