GFE Cummins-Powered 700kVA Diesel Generator - GFE770CSC
The GFE770CSC is rated at 770kVA standby power and delivers 700kVA of prime power, providing reliable electricity for demanding industrial and commercial applications. Powered by a Cummins KTA38-GA engine and paired with a Stamford S5L1D-GA alternator, it ensures efficient and stable performance. Operating at 50Hz, 1500rpm, and 400V with a rated current of 1010 amps, it is well suited for continuous and backup power needs. The generator is housed in a durable canopy with a 1000-litre base fuel tank and uses a Deepsea DSE6120 control panel for easy monitoring and control.
| Model reference | GFE770CSC (Canopied) |
| Engine | Cummins KTA38-GA |
| Alternator | Stamford S5L1D-GA |
| Control panel | Deepsea DSE6120 |
| Frequency | 50Hz |
| Engine speed | 1500rpm |
| Phase / Poles | 3-Phase / 4-Pole |
Ratings
| kWe | kVA | |
| Prime Power (PRP) | 560 | 700 |
|
Standby Power (ERP) |
615 | 770 |
|
Voltage |
400V |
| Rated current | 1010 Amps |
| Fuel consumption | @100% load L/h 160 |
Overall dimensions
| Frame type | Dimensions | Weight | Base tank @100% load |
| (L x W x H) mm | kg | Litres | |
| Canopied | 5450 x 2270 x 2550 | 9800 | 1000 |
Datasheets
| Generator: | Engine: | Alternator: |
| 700kVA GFE770CSC | Cummins KTA38-GA | Stamford S5L1D-G4 |
![]() |
![]() |
![]() |
Choose options


Unsure What Size Generator You Need?
Selecting the correct generator size starts with understanding your power requirements. Our kVA calculator allows you to calculate the kVA needed based on your power requirements, helping you choose a generator that fits your application.